Check Valve Series

Product drawing»

Structural drawing»

You are here: News > News Detail

Yipump Valve H71X-16P Wafer Check Valve: Pressure and Temperature Parameters plus Installation Instructions

2026-11-23

The short face-to-face length and single-disc design make this valve suitable for pipelines where installation space is limited, and the spring-assisted closure helps reduce water hammer when flow reverses.

Pressure and Temperature ParametersThe main check valve product names of China Check Valve Network include:Two-plate Tiny Drag Slow Close Butterfly Check Valve,Energy-saving Muffler Check Valve,Flange Silent Check Valve,Wafer Silent Check Valve,Chute Rolling-ball Check Valve,Flange Swing Rubber Disc Check Valve,Oversized Silent Check Valve,Flange Ball Check Valve.

The H71X-16P carries a nominal pressure rating of PN16, equivalent to 1.6 MPa. The shell test pressure is 2.4 MPa, and the seal test pressure is 1.76 MPa. The working temperature limit depends on the sealing material. For the standard soft-seated H71X version with rubber sealing, the applicable temperature is generally stated as up to 80 degrees Celsius, while stainless steel models with suitable seals can be rated higher. The H71W-16P variant with a metal or PTFE seat is commonly listed at up to 200 degrees Celsius. Some catalogs list a broader range of minus 40 to 180 degrees Celsius for the H71 wafer family, but the actual limit should always be confirmed against the specific seal compound supplied. The valve is intended for water, steam, oil, and non-aggressive media, and it should not be used outside the pressure and temperature limits marked on the nameplate.

Installation Instructions

Before installation, verify the valve size, pressure rating, and body condition. Press the disc by hand to confirm it moves freely without sticking. Check the arrow on the valve body and make sure it points in the direction of normal flow; reverse installation will prevent the valve from closing and can cause leakage.

The H71X-16P can be installed in both horizontal and vertical pipelines, but the preferred orientation depends on the line layout. In horizontal piping, the valve axis should be kept vertical so that the disc closes by gravity in addition to spring force. When the valve is clamped between flanges, tighten the bolts evenly and in a cross pattern. Do not over-tighten one side, because uneven clamping force can distort the body and damage the seat. The valve should not be used to support the weight of the pipeline; large sizes should be independently supported. Avoid installing reducers directly at the valve inlet or outlet, and keep the disc operation radius free of fittings or obstructions. When the valve is fitted at a pump discharge, provide at least six times the valve diameter of straight pipe upstream so that the disc receives stable flow before closing.

Do you still need to know or purchase the following check valve products:

 Kaiweixi Valve Group Co., Ltd.
Kaiweixi check valve Contact Kaiweixi
Zhejiang Shanliu Valve Technology Co., Ltd.
Shanliu Check Valve Contact Shanliu
Shanghai FengQi Industrial Development CO., Lid.
FengQi Check Valve Contact FengQi
Shanghai MeiYan Yi Pump & Valve Co., Ltd.
MeiYan Yi check valve Contact MeiYan Yi