Check Valve Series

Product drawing»

Structural drawing»

You are here: News > News Detail

SELECTING A VALVE TYPE

2010-10-20

So how do you decide which valve control to use? Here are some rules of thumb for each one: 1. Equal Percentage (most commonly used valve control) a. Used in processes where large changes in pressure drop are expected b. Used in processes where a small percentage of the total pressure drop is permitted by the valve c. Used in temperature and pressure control loops 2. Linear a. Used in liquid level or flow loops b. Used in systems where the pressure drop across the valve is expected to remain fairly constant (ie. steady state systems) 3. Quick Opening a. Used for frequent on-off service b. Used for processes where "instantly" large flow is needed (ie. safety systems or cooling water systems) Now that we've covered the various types of valve control, we'll take a look at the most common valve types. Gate Valves Best Suited Control: Quick Opening

MORE NEWS

  • Check the gain across applicable flowrates
  • Check the Cv and stroke percentage at the minimum flow
  • Preliminary valve selection
  • General Chemical Engineering References
  • Shanghai MeiYan Yi Pump & Valve Co., Ltd.
    MeiYan Yi check valve Contact MeiYan Yi
    Shanghai Enine Pump & Valve Co., Ltd.
    Enine check valve Contact Enine
    Shanghai Saitai Pump & Valve CO., Lid.
    Saitai Check Valve Contact Saitai
    Shanghai FengQi Industrial Development CO., Lid.
    FengQi Check Valve Contact FengQi