Check valve at floor control valve
What is the purpose of the check valve in Figure A.8.17.5.2.2(b)?
8.17.5.2.2* The following restrictions shall apply:
(1)
Each connection from a standpipe that is part of a combined system
to a sprinkler system shall have an individual control valve and check
valve of the same size as the connection.
(2) The minimum size of
the riser shall be 4 in. (102 mm) unless hydraulic calculations
indicate that a smaller size riser will satisfy sprinkler and hose
stream allowances.
(3) Each combined sprinkler and standpipe
riser shall be equipped with a riser control valve to permit isolating a
riser without interrupting the supply to other risers from the same
source of supply. (For fire department connections serving standpipe and
sprinkler systems, refer to Section 6.8.)